    The world's most reliable power protection ® Matrix TM UPS Hard-wire kit accessory MXA001 MXA002 User's Manual American Power Conversion ...

  • American Power Conversion MXA002 - page 2

    Important safety instructions! Please read this manual! V euillez lire ce manuel! Bitte lesen Sie dieses Anleitungshandbuch! ¡Se ruega leer este manual de instrucciones! PLEASE SA VE THIS MANUAL ! It includes important instructions for the safe use and installation of the UPS and its accessories. CONSERVER CES INSTRUCTIONS ! Cette notice contient ...

  • American Power Conversion MXA002 - page 3

    Page 1 T able of contents 1.0 Introduction ................................................................................. 2 2.0 Presentation ................................................................................. 3 3. 0 Installation ................................................................................... 4 Input voltage requ ...

  • American Power Conversion MXA002 - page 4

    Page 2 1.0 Introduction The hard-wire kit allows the UPS's input and/or output terminals to be permanently secured to building service wiring. This kit is used in place of the power distribution plate and/or input cable plate originally furnished with the UPS. The kit contains input cable and output power distribution plates with "knock-o ...

  • American Power Conversion MXA002 - page 5

    Page 3 2.0 Presentation Power distribution plate Provides an interface for output hard-wiring of loads. It is used in place of the power distribution plate for cord connected equipment originally furnished with the UPS. Input cable plate Used to replace the input cable plate originally furnished with the UPS. It allows hard-wiring of the input conn ...

  • American Power Conversion MXA002 - page 6

    Page 4 3.0 Installation ■ W arning: Risk of electric shock exists inside the UPS. Input voltage tap selection and power distribution panel replacement should be performed only by qualified service personnel. ■ A vertissement: Un risque de choc électrique existe à lintérieur de lUPS. La sélection des fils de tension dentrée et le r ...

  • American Power Conversion MXA002 - page 7

    Page 5 3.0 Installation T able 3.2.1 Cable Size S tri p Length UP S M ode l Min im um Ma x i m um Input cable Output cable 300 0VA 2. 5 m m 2 12 A W G 1 0 .0 m m 2 8 AW G 12 m m 1/2" 9 m m 3/8" 500 0VA 6. 0 m m 2 10 A W G 1 0 .0 m m 2 8 AW G ■ Cable clamps The UPS is not furnished with cable clamps for strain relief. Use only approved ? ...

  • American Power Conversion MXA002 - page 8

    Page 6 3.0 Installation Input cable connections 3.3 Input wiring procedure - continued T o remove a knock-out, strike in the area shown with a nail set tool and hammer . Grasp the edge of the knock-out with pliers and twist until the knock-out is separated from the plate. Caution: The edge of the knock-out may be sharp! Example showing removal of ? ...

  • American Power Conversion MXA002 - page 9

    Page 7 3.0 Installation 3.3 Input wiring procedure - continued 3.3.4 Remove all three input cable wire connections from terminal block labeled L1 , and L2/N . 3.3.5 Remove all screws that secure the input cable plate. Use a pair of wire cutters to remove "tie wraps" binding the input cable to wires inside the Isolation Unit. T ake care no ...

  • American Power Conversion MXA002 - page 10

    Page 8 Unmating of UPS output power connector 3.0 Installation 3.4 Output wiring procedure 3.4.1 Be sure the input circuit breaker is switched off (0) and the input cable is unplugged and/ or has no power applied. Caution: Switching the circuit breaker to off (0) does not remove power to all of the Isolation Unit. Power to the UPS must be disconnec ...

  • American Power Conversion MXA002 - page 11

    Page 9 Diagram showing power distribution plate earth connection 3.0 Installation 3.4 Output wiring procedure - continued 3.4.4 Use a 3/8" wrench to remove the protective earth wire (green with yellow stripes) ring terminal fastened at the earthing stud on the Isolation Unit. 3.4.5 Remove the desired knock-out from the new power distribution p ...

  • American Power Conversion MXA002 - page 12

    Page 10 3.0 Installation 3.4 Output wiring procedure - continued 3.4.9 Choose the desired wiring connections from the illustrations on the following pages (Figure 3.4.1 through Figure 3.4.6 ). Insert the stripped wire ends into the appropriate output terminations block terminal and tighten the terminal screws. Caution: Overcurrent protection for ou ...

  • American Power Conversion MXA002 - page 13

    Page 11 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.1 1 f , 208 V ac loads only 3000 V A model with MXA002 hard- wire kit: 15 Amp maximum. 5000 V A model with MXA001 hard- wire kit: 24 Amp maximum. Figure 3.4.2 1 f , 240 V ac loads only 3000 V A model with MXA002 hard- wire kit: 12.5 Amp maximum. 5000 V A model with MXA001 h ...

  • American Power Conversion MXA002 - page 14

    Page 12 3.0 Installation 3.4 Output wiring procedure - continued Figure 3.4.5 1 f , 120/240 V ac loads ■ ■ ■ ■ ■ 3000 V A model with MXA002 hard- wire kit Each 120 V ac output: 25 Amp maxi- mum. 240 V ac output: 12.5 Amp maximum. T otal output: not to exceed 3000 V A . ■ ■ ■ ■ ■ 5000 V A model with MXA001 hard- wire kit Each 120 ...

  • American Power Conversion MXA002 - page 15

    Limited W arranty American Power Conversion (APC) warrants its products to be free from defects in materials and workmanship for a period of two years from the date of purchase. Its obligation under this warranty is limited to repairing or replacing, at its own sole option, any such defective products. To obtain service under warranty you must obta ...

  • American Power Conversion MXA002 - page 16

    Customer Service Note: Before calling the customer service number , please have available your UPS's serial number (see the label at the rear of the UPS). ( PHONE (+33) 1.64.62.59.00 in Europe (401) 789-5735 world wide * MAILING American Power Conversion 4, rue Ste Claire Deville Zac du Mandinet-Bâtiment Espace LOGNES 77447 MARNE LA V ALLEE C ...

メーカー American Power Conversion カテゴリー Power Supply

American Power Conversion MXA002のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- MXA002の取扱説明書
- American Power Conversionの製品カード
- パンフレット
- またはAmerican Power Conversion MXA002の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、American Power Conversion MXA002の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、American Power Conversion MXA002の取り付け説明書、サービスマニュアル、簡易説明書、またはAmerican Power Conversion MXA002のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、American Power Conversion MXA002の製品を使用するにあたって最も人気のある説明書を閲覧できます。

American Power Conversion MXA002デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがAmerican Power Conversion MXA002を使用するのを助ける技術的文書のことです。説明書は通常、全てのAmerican Power Conversion MXA002ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

American Power Conversionの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. American Power Conversion MXA002の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははAmerican Power Conversion MXA002の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。American Power Conversion MXA002に関してこのドキュメントで見つけることができる全てのヒントの目次
3. American Power Conversion MXA002デバイスの基本機能を使うにあたってのヒント。 American Power Conversion MXA002のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。American Power Conversion MXA002に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるAmerican Power Conversion MXA002のメーカー/サービスへの連絡先に関する情報。

American Power Conversion MXA002についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもAmerican Power Conversion MXA002の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがAmerican Power Conversion MXA002で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)