    OPERATING INSTRUCTIONS AND S PECIFICA TIONS NI 9472/9474 8-Channel Digital Output Modules ni.com/manuals Deutsch Français ...

  • National Instruments NI 9472 - page 2

    NI 9472/9474 2 ni.com This doc u ment describes ho w to u se the National Instr u ments 9472 and National Instr u ments 9474 and incl u des specif ications and terminal or pin assignments. In this doc u ment, the NI 94 72/9474 with screw terminal and NI 9472 with DSUB are referred to incl u siv ely as the NI 9472/9474. V isit ni.com/info and enter ...

  • National Instruments NI 9472 - page 3

    © National Instruments Corp. 3 NI 9472/9474 Hot Surface This icon denotes that the component may be hot. T o u ching this component may res u lt in bodily inj u ry . Safety Guidelines for Hazardous V oltages Yo u can connect hazardo u s voltages only to th e NI 9472/9474 with screw terminal. Do not connect hazardo u s v oltages to the NI 9472 with ...

  • National Instruments NI 9472 - page 4

    NI 9472/9474 4 ni.com and circ u its connected to the mod u le are properly ins u lated from h u man contact. Y o u m u st u se the NI 9932 connector backshell kit to ens u re that the terminals are not accessible. Fig u re 1 sho ws the NI 9932 connector backshell. Note Yo u can u se the NI 9932 connec tor bac ksh ell o nly with th e NI 9472/9474 w ...

  • National Instruments NI 9472 - page 5

    © National Instruments Corp. 5 NI 9472/9474 Safety Guidelines fo r Hazardous Loca tions The NI 9472/9474 is s u itable for u se in Class I, Di vision 2, Gro u ps A, B, C, D, T4 hazardo u s locations; Class I, Zone 2, AEx nC IIC T4 and Ex nC IIC T4 hazardo u s locations; and nonhazardo u s locations only . Follow these g u idelines if yo u are inst ...

  • National Instruments NI 9472 - page 6

    NI 9472/9474 6 ni.com Caution For Zone 2 applications, install a protection device between the V s u p and COM terminals on the NI 9472/9474. The d evice m u st pre vent the inp u t V s u p -to-COM voltage from e xceeding 42 V i f there is a transient overv oltage condition. Special Conditions for Hazard ous Locations Use in Europe This eq u ipment ...

  • National Instruments NI 9472 - page 7

    © National Instruments Corp. 7 NI 9472/9474 Special Conditions fo r Marine Applicatio ns Some mod u les are Lloyd’ s Register (LR) T ype Approved for marine applications. T o verify Llo yd’ s Register cert ification, visit ni.com/certification and search for the LR certificate, or look for the Lloyd’ s Register mark on the mod u le. Caution ...

  • National Instruments NI 9472 - page 8

    NI 9472/9474 8 ni.com Connecting the NI 9472/9474 The NI 9472/9474 provides connectio ns for eight digital o u tp u t channels. Figure 2. NI 9472/9474 T erminal and Pin Assignments DO0 DO1 DO2 DO3 DO4 DO5 DO6 DO7 Vsup COM 0 1 2 3 4 5 6 7 8 9 COM Vsup COM COM Vsup COM COM Vsup COM COM Vsup COM COM DO0 Vsup DO1 DO2 Vsup DO3 DO4 Vsup DO5 DO6 Vsup DO7 ...

  • National Instruments NI 9472 - page 9

    © National Instruments Corp. 9 NI 9472/9474 The NI 9472/9474 with scre w te rminal has a 10-terminal, detachable scre w-terminal conne ctor . The NI 9472 with DSUB has a 25-pin DSUB connector . Each channel of the NI 9472/9474 has a terminal or pin, DO, to which yo u can connect a device. The eight digital o u tp u t channels are inte rnally refer ...

  • National Instruments NI 9472 - page 10

    NI 9472/9474 10 ni.com Yo u m u st connect an external po wer s u pply to the NI 9472/9474. This power s u pply provides the c u rrent for the de vices yo u connect to the mod u le. Connect the positi ve lead of the po wer s u pply to V s u p and the negati v e lead of the power s u pply to COM. The V s u p pins on the NI 9472 with DSUB ar e intern ...

  • National Instruments NI 9472 - page 11

    © National Instruments Corp. 11 NI 9472/9474 Yo u can directly connect the NI 9472/9474 to a v ariety of ind u strial de vices s u ch as solenoids, motors, act u ators, relays, and lamps. Make s u re the devices yo u connect to the NI 9472/9474 are compatible with the o u tp u t specificati ons of the mod u le. Refer to the Specifications section ...

  • National Instruments NI 9472 - page 12

    NI 9472/9474 12 ni.com Increasing Current Drive Each channel of the NI 9472 has a contin u o u s o u tp u t c u rrent of 0.75 A, and each channel of the NI 9474 has a contin u o u s o u tp u t c u rrent of 1 A. If yo u want to increase the o u tp u t c u rrent to a de vice, yo u can connect any n u mber of channels together in parallel. For e xampl ...

  • National Instruments NI 9472 - page 13

    © National Instruments Corp. 13 NI 9472/9474 Wiring for High-Vibration Applications If an application u sing the NI 9472/9474 with screw terminal is s u bject to high vibrat ion, National Instr u ments recomm ends that yo u either u se ferr u les to terminate wires to the detacha ble scre w-terminal connector or u se the NI 9932 backshell kit to p ...

  • National Instruments NI 9472 - page 14

    NI 9472/9474 14 ni.com I/O Protection The NI 9472/9474 is short-circ u it proof in accordan ce with IEC 1131-2 and provides o verc u rren t protection. Understanding Sh ort-Ci rcuit-Proof Devices Each channel on the NI 9472/9474 has circ u itry that protects it from c u rrent s u rge s r es u lting from short circ u its. Whet her the mod u le s u f ...

  • National Instruments NI 9472 - page 15

    © National Instruments Corp. 15 NI 9472/9474 more informatio n abo u t the maxim u m contin u o u s o u tp u t c u rrent, short-circ u it behavior , and short-circ u it trip time. Y o u also can refer to the IEC 1131-2 standard for more information abo u t short-circ u it-proof de vices. Tip Beca u se the NI 9472/947 4 mod u le incl u des internal ...

  • National Instruments NI 9472 - page 16

    NI 9472/9474 16 ni.com the channel is in an overc u rrent state, meas u re the voltage between DO and V s u p . If the v oltage is eq u al to the volta ge of the exte rnal power s u pply connected to the mod u le, the channel is in an ove rc u rrent state. Resetting Channels After an Overcurrent Condition After yo u hav e determined and fixed the c ...

  • National Instruments NI 9472 - page 17

    © National Instruments Corp. 17 NI 9472/9474 T ypically , when a system is in sleep mode, yo u cannot comm u nicate with the mod u les. In sleep mode, the system cons u mes minimal po wer and may diss ipat e less heat than it does in normal mode. Refer to the Specifications section for more information abo u t power cons u mption and thermal dissi ...

  • National Instruments NI 9472 - page 18

    NI 9472/9474 18 ni.com O u tp u t impedance ( R 0 ) T ypical . ............. ............ ............. . 0.07 Ω Maxim u m ......... .............. ........... . 0.13 Ω Contin u o u s o u tp u t c u rrent ( I 0 ), per channel NI 9472 ......... ...................... ........ 0.75 A max NI 9474 ........... .................. .......... 1 A max O u ...

  • National Instruments NI 9472 - page 19

    © National Instruments Corp. 19 NI 9472/9474 O u tp u t delay time (f u ll load) NI 9472 ........... ........... ............ ..... 100 μ s max NI 9474 ......... ...................... ........ 1 μ s max MTBF NI 9472 ......... ...................... ........ 1,113,301 ho u rs at 25 °C; Bellcore Iss u e 2, Method 1, Case 3, Limited P art Stress ...

  • National Instruments NI 9472 - page 20

    NI 9472/9474 20 ni.com Thermal dissipation (at 70 °C) Active mode ............ .............. ..... 1.5 W max Sleep mode .......... ........... ........... . 55 mW ma x NI 9474 Power Requirem ents Power cons u mption fr om chassis Activ e mode .............. .............. ... 660 mW max Sleep mode .......... ........... ........... . 0.6 mW ma x ...

  • National Instruments NI 9472 - page 21

    © National Instruments Corp. 21 NI 9472/9474 Ferr u les ........ ........... .............. ........... . 0.25 mm 2 to 2.5 mm 2 W eight NI 9472/9474 with screw terminal .. ............ ............. . 150 g (5.3 oz) NI 9472 with DSUB ......... .......... 145 g (5.1 oz) Safety NI 9472/9474 with Screw T erm inal Safety Voltages Connect only v oltage ...

  • National Instruments NI 9472 - page 22

    NI 9472/9474 22 ni.com This cate gory refers to local-le vel electrical distr ib u tion, s u ch as that provided b y a standard wall o u tlet, for e xample, 115 V for U.S. or 230 V for E u rope. Caution Do not connect the NI 9472 /9474 with screw terminal to signals or u se for meas u rements within Meas u rement Categories III or IV . NI 9472 with ...

  • National Instruments NI 9472 - page 23

    © National Instruments Corp. 23 NI 9472/9474 s u pply system that powers eq u ipment. This cate gory is for meas u rements of voltages from spec ially protecte d secondary circ u its. S u ch v oltage meas u rements incl u de signal le vels, special eq u ipment, limited-ene rg y parts of eq u ipment , circ u its po wered by reg u lated lo w-voltage ...

  • National Instruments NI 9472 - page 24

    NI 9472/9474 24 ni.com Hazardous Locations U.S. (UL) .......... ........... ............. ........ Class I, Division 2, Gro u ps A, B, C, D, T4; Class I, Zone 2, AEx nC IIC T4 Canada (C-UL) ............ ........... .......... Cla ss I, Division 2, Gro u ps A, B, C, D, T4; Class I, Zone 2, Ex nC IIC T4 E u rope (DEMK O)........ ........... ......... ...

  • National Instruments NI 9472 - page 25

    © National Instruments Corp. 25 NI 9472/9474 Environmental National Instr u ments C Series mod u les are intend ed for indoor u se only b u t may be u sed o u tdoors if installed in a s u itabl e enclos u re. Refer to th e man u al for the chassis yo u are u sing for more information abo u t meeting th ese specif ications. Operating temperat u re ...

  • National Instruments NI 9472 - page 26

    NI 9472/9474 26 ni.com Shock and Vibration T o meet th ese specifications, yo u m u st panel mo u nt the system. If yo u are u sing the NI 9472/9474 with scre w terminal, yo u also m u st either af fix ferr u les to the ends of the terminal wires or u se the NI 9932 backshell kit to protect the connections. Operating vibration Random (IEC 60068-2-6 ...

  • National Instruments NI 9472 - page 27

    © National Instruments Corp. 27 NI 9472/9474 Note For EMC compliance, operate this de vice with shielded cabling. CE Compliance This prod u ct meets the essent ial req u irem ents of applic able E u ropean directi ves, as amended for CE markings, as follo ws: • 2006/95/EC; Low-V oltage Directi ve (safety) • 2004/108/EC; Electromagneti c Compat ...

  • National Instruments NI 9472 - page 28

    NI 9472/9474 28 ni.com Environmental Mana gement National Instr u ments is committe d to designing and man u fact u ring prod u cts in an en vironmentally res ponsible manner . NI recognizes that eliminating certain hazardo u s s u bstan ces from o u r prod u cts is beneficial not only to t he en vironment b u t also to NI c u stomers. For addition ...

  • National Instruments NI 9472 - page 29

    © National Instruments Corp. 29 NI 9472/9474 Where to Go for Support The National Instr u ments W eb site is yo u r complete reso u rce for technical s u pport. At ni.com/ s upport yo u have access to ev erything from tro u bleshooting and applic ation dev elopment self-help reso u rces to email and phone assistance from NI Application Engineers. ...

  • National Instruments NI 9472 - page 30

    NI 9472/9474 30 ni.com telephone s u pport o u tside the United St ates, contact yo u r local branch off ice: A u stralia 1800 300 800, A u stria 43 662 457990-0, Belgi u m 32 (0) 2 757 0020, Brazil 55 11 3262 3599, Canada 800 433 3488, China 86 21 5050 9800, Czech Rep u blic 420 224 235 774, Denmark 45 45 76 2 6 00, Finland 358 (0) 9 725 72511, Fr ...

  • National Instruments NI 9472 - page 31

    © 2003–2008 Nati onal Instruments Corp. All rights reserved. 373509E-01 May08 National Instruments, NI, n i.com, and LabVIEW are tr ademarks of National Instrument s Corporation. Refer to the Terms of Use section on ni.com/legal for more information about Natio nal Instruments trademarks. Other product and company names ment ioned herein are tra ...

Manufacturer National Instruments Category Network Card

Documents that we receive from a manufacturer of a National Instruments NI 9472 can be divided into several groups. They are, among others:
- National Instruments technical drawings
- NI 9472 manuals
- National Instruments product data sheets
- information booklets
- or energy labels National Instruments NI 9472
All of them are important, but the most important information from the point of view of use of the device are in the user manual National Instruments NI 9472.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals National Instruments NI 9472, service manual, brief instructions and user manuals National Instruments NI 9472. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product National Instruments NI 9472.

A complete manual for the device National Instruments NI 9472, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use National Instruments NI 9472 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of National Instruments NI 9472.

A complete National Instruments manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual National Instruments NI 9472 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the National Instruments NI 9472, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the National Instruments NI 9472, that we can find in the current document
3. Tips how to use the basic functions of the device National Instruments NI 9472 - which should help us in our first steps of using National Instruments NI 9472
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with National Instruments NI 9472
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of National Instruments NI 9472 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning National Instruments NI 9472?

Use the form below

If you did not solve your problem by using a manual National Instruments NI 9472, ask a question using the form below. If a user had a similar problem with National Instruments NI 9472 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)